Figure11-TerminalUsingPhoneModems
SHIELD
DONOTCONNECT
ATTHISEND
VDT
MODEMSWITCHSETTINGS MODEMSWITCHSETTINGS
CORBYSERIALPRINTERANSI
VIDEODISPLAYTERMINAL
TODIAL-UP
PHONELINE
ATSYSTEM2LOCATION
TODIAL-UP
PHONELINE
ATVDTLOCATION
MALEDB25
CONNECTOR
MODEM
PORT
PHONE
MODEM
MODULAR
PHONE
CORD
MODULAR
PHONE
CORD
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
PLUGINTO
AUXPORT
NOTES:
THERS232OPTIONMUSTBEACTIVATEDTOPROGRAMWITHAVDTORPC
RS232DEFAULTSETTINGS:9600BAUD,8DATABITS,1STOPBIT,NOPARITY
DONOTCONNECTTHEPRINTERORVDTTOARECEPTACLECONTROLLEDBYASWITCH
YOUMUSTENTERSET-UPONTHEVDTPRESS<F3>,THENPRESS<F2>ANDCHANGETHEVDTPERSONALITYTOVT100.
TOEXITANDSAVESETTINGS:PRESSF12,TOGGLETOYES,PRESSF12AGAIN.
TOACTIVATETHEAUXPORTFORTHEPRINTERPRESS.AUXWILLAPPEARATTHETOPOFTHEVDT.SHIFTCTRLPRINT
ON
OFF
OFF
ON
OFF
ON
RS-232
9PINMALE
CONNECTOR
(P1)
USEFOR
ATERMINAL,
PCORMODEM
9PINFEMALE
CONNECTOR
BLUE
RED
WHITE
BLACK
GREEN
BROWN
4
3
2
7
5
8
ASTANDARDMODEMCABLEISALLTHATISREQUIRED
FORCONNECTIONFROMTHESYSTEM2TOAMODEM.
(9PINFEMALETO25PINMALE).
SOLDERSHIELDOF
CABLETO9PIN
CONNECTORCASE