CHAPTER 2
QUICKSTART
Bench Test
U Power up. Connect supplied transformer to Terminals #2 and #3. Then connect supplied battery to H1, see
Figure 8. The AC LED should be on solid and the ACTIVITY LED should be flashing. The +5V, +6V,
+12V, and CTS LEDs should be on solid. See Figure 5 for LED locations. The LCD should be prompting you
to clear memory now.
U Enter default initialization setup:
Clear memory - Press ## on the programing keypad. The Required Events prompt will display on the LCD.
Use the default of 100 events - Press #. The Temporary Users prompt will display on the LCD.
Use the default of 10 temporary users - Press #. The Allow User Names prompt will display on the LCD.
Use the default of no names - Press #. The Allow Networking prompt will display on the LCD.
Use the default of no network - Press # on the LCD.
The System is now initialized, the power up events will be displayed on the LCD.
U Test RTE - Momentarily connect a jumper across Terminals #22 and #27. Use the terminals on the left hand
side of the circuit board - Port A. The Door relay should activate and the LCD should display an RTE event.
U Test Forced Entry -Momentarily connect a jumper across Terminals #22 and #26 of Terminal block “A”. A
Door Closed event should be displayed on the LCD. Then a Forced Entry event should be displayed on the
LCD.
U Test Zone Input -Momentarily connect a jumper across Terminals #22 and #37. A Zone ON event should be
displayed on the LCD. Then a Zone OFF event should be displayed on the LCD.