PC/VDT PROGRAMMING - TIME SCHEDULES
9-178
System 2 Installation / Programming Manual
Now for a final note. What would this have looked like if, instead of granting or denying access
to users, we had instead wanted to unlock and lock a door? The beauty of this schedule system
is that we would simply have assigned the same schedule to a door instead of a user. In this
case, the door would have unlocked at 08:00 and locked at 18:00 Monday through Friday, and
would have remained locked on Christmas and New Year's Day. Later in this manual, we'll see
the mechanics of how to actually assign schedules. Now to programming schedules.
Choosing the Schedule
The first thing you will do is select which schedule you want to program.
The VDT will display the following instructions:
Enter Schedule #
Use 1 thru 8
0=Quit
Choose Schedule [_0]
At the Choose Schedule [ _ 0 ] prompt enter the schedule you want. Pressing 0
then ENTER to exit this option. If you wish to start with Schedule #1 press 1 then ENTER.
Note: If you have a two-door System 2 (2016) , the amount of schedules available is 16.
Choosing the Time Cell
After selecting the schedule, select that schedule's time cells you wish to program.
The VDT will display the following instructions:
This Schedule=01
Use 1 thru 32
0=Quit
Choose Schedule [_0]
Note: If you have a two-door System 2 (2016), the amount of schedules available is 16,
and the amount of time cells in each schedule increases to 64.
At the Choose Time Cell [ _ 0 ] prompt, pick the time cell you want. If you pick 0,
you will be returned to the Choose Schedule prompt, at which point you can select a new
schedule to program or you can leave the option by again selecting 0 then pressing ENTER.
Let’s say you wish to program cell #1, simply press 1 and ENTER. All initial programming of
cells must be entered sequentially (Cell #1 must be entered before Cell #2, etc.).
If you create an “ON” cell, you should have a corresponding “OFF” cell. Otherwise, the cell
will turn something on and never turn it off. This may be a condition you desire. If so, to turn it
off, you must use Main Menu Option 14.